N2XB(AL)Y 1 x ( 16 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
10 11.4 215
16 12.5 289
25 14.1 396
35 15.2 503
50 16.8 633
70 18.7 851
95 20.5 1,117
120 22.3 1,375
150 24.2 1,650
185 26.4 2,103
240 29.3 2,609
300 32.5 3,273
 

ELECTRICAL DATA

Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
       
mm² Ω/km Ω/km A A A A mH/km kA
10 1.83 2.340 91 91 112 112 0.248 1.43
16 1.15 1.470 99 114 122 122 0.238 2.29
25 0.727 0.930 137 154 143 156 0.240 3.58
35 0.387 0.671 161 189 168 183 0.233 5.01
50 0.268 0.495 201 228 198 218 0.232 7.15
70 0.193 0.319 250 289 243 267 0.229 10.01
95 0.153 0.247 311 356 293 322 0.224 13.59
120 0.124 0.196 368 417 332 367 0.223 517.16
150 0.0991 0.159 423 479 376 416 0.224 21.45
185 0.0754 0.127 490 557 427 466 0.225 26.46
240 0.0601 0.0965 590 657 285 535 0.223 34.32
300 0.153 0.0769 679 758 545 615 0.221 42.90