N2XB(AL)Y 2 x ( 16 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 12.9 215
2.5 13.5 273
4 14.4 326
6 15.4 395
10 18.1 508
16 20.3 679
25 23.6 939
35 25.8 1,179
50 29.2 1,507
70 33.7 2,065
95 38.7 2,780
120 42.5 3,425

 

 

ELECTRICAL DATA

Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 15.429 27 33 0.315 0.21
2.5 7.41 9.449 36 44 0.293 0.36
4 4.61 5.878 48 58 0.275 0.57
6 3.08 3.927 61 72 0.263 0.86
10 1.83 2.334 83 97 0.248 1.43
16 1.153 1.466 113 128 0.238 2.29
25 0.727 0.927 150 167 0.240 3.58
35 0.524 0.668 186 201 0.233 5.01
50 0.387 0.494 226 239 0.232 7.15
70 0.268 0.342 290 295 0.229 10.01
95 0.193 0.247 353 355 0.224 13.59
120 0.153 0.196 413 404 0.223 17.16
150 0.124 0.160 468 458 0.224 21.45
185 0.0991 0.128 540 516 0.225 26.46
240 0.0754 0.099 590 600 0.223 34.32
300 0.0601 0.080 745 695 0.221 42.90