N2XB(AL)Y 4 x ( 16 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 13.4 263
2.5 14.3 321
4 15.4 400
6 16.7 507
10 19.8 736
16 22.5 995
25 26.4 1,421
35 29.4 1,863
50 33.6 2,462
70 39.3 3,457
95 44.7 4,663
120 49.2 5,760
150 54.1 6,975
185 61.3 9,042
240 67.5 11,174
300 74.8 13,929

 

 
 
 

ELECTRICAL DATA

Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 15.429 26 29 0.315 0.21
2.5 7.41 9.449 32 38 0.293 0.36
4 4.61 5.878 41 49 0.275 0.57
6 3.08 3.927 52 60 0.263 0.86
10 1.83 2.334 71 97 0.248 1.43
16 1.153 1.466 96 108 0.238 2.29
25 0.727 0.927 130 141 0.240 3.58
35 0.524 0.668 159 170 0.233 5.01
50 0.387 0.494 193 201 0.232 7.15
70 0.268 0.342 245 249 0.229 10.01
95 0.193 0.247 302 299 0.224 13.59
120 0.153 0.196 349 340 0.223 17.16
150 0.124 0.160 400 381 0.224 21.45
185 0.0991 0.128 464 434 0.225 26.46
240 0.0754 0.099 552 506 0.223 34.32
300 0.0601 0.080 640 585 0.221 42.90