NA2XY 1 x ( 1.5 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 6.0 46
2.5 6.2 59
4 6.7 77
6 7.5 104
10 8.0 142
16 9.5 213
25 11.5 318
35 12.5 419
50 14.0 546
70 16.0 766
95 18.0 1,033
120 20.0 1,287
150 22.0 1,575
185 25.0 1,965
240 28.0 2,552
300 31.0 3,071

 

 
 
 
 

ELECTRICAL DATA

Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
       
mm² Ω/km Ω/km A A A A mH/km kA
1.5 12.1 15.429 39 35 54 43 0.498 0.21
2.5 7.41 9.449 48 43 73 58 0.463 0.36
4 4.61 5.878 63 57 95 76 0.433 057
6 3.08 3.927 80 72 119 95 0.410 0.86
10 1.83 2.334 108 98 161 128 0.382 1.43
16 1.15 1.466 146 132 212 169 0.361 2.29
25 0.727 0.927 207 187 276 220 0.348 3.58
35 0.524 0.668 240 217 333 265 0.335 5.01
50 0.387 0.494 291 263 397 316 0.325 7.15
70 0.268 0.342 366 331 483 385 0.316 10.01
95 0.193 0.247 451 408 584 465 0.310 13.59
120 0.153 0.196 524 474 667 531 0.305 17.16
150 0.124 0.160 608 550 750 597 0.305 21.45
185 0.0991 0.128 700 633 854 680 0.304 26.46
240 0.0754 0.099 830 750 992 790 0.300 34.32
300 0.0501 0.080 963 871 1131 901 0.295 42.90