N2XY 3 x ( 1.5 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 12.0 207
2.5 13.0 266
4 14.1 339
6 15.4 426
10 17.3 597
16 19.5 829
25 23.1 1,224
35 24.4 1,586
50 25.5 1,642
70 28.3 2,404
95 31.6 3,255
120 34.8 4,067
150 38.7 4,950
185 43.3 6,184
240 48.4 7,976
300 54.0 9,940

 

 
 
 
 

ELECTRICAL DATA

Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 15.429 27 33 0.315 0.21
2.5 7.41 9.449 36 44 0.293 0.36
4 4.61 5.878 48 58 0.275 0.57
6 3.08 3.927 61 72 0.263 0.86
10 1.83 2.334 83 97 0.248 1.43
16 1.153 1.466 113 1288 0.238 2.29
25 0.727 0.927 150 167 0.240 3.58
35 0.524 0.668 186 201 0.233 5.01
50 0.387 0.494 226 239 0.232 7.15
70 0.268 0.342 290 295 0.229 10.01
95 0.193 0.247 353 355 0.224 13.59
120 0.153 0.196 413 404 0.223 17.16
150 0.124 0.160 468 458 0.224 21.45
185 0.0991 0.128 540 516 0.225 26.46
240 0.0754 0.099 590 600 0.223 34.32
300 0.0501 0.080 745 695 0.221 42.90