NA2XY 5 x ( 1.5 - 300 ) mm2 0.6/1 kV
AL/XLPE/PVC
( Aluminium Conductor, XLPE Insulated, PVC Sheathed )
Standard Specification : SNI IEC 60502 - 1
Aplication :
Power cable : Indoors, cable trunking, outdoors and burried in the ground
for power stations, industry and switchgear as well as
for urban supply networks, if mechanical damage is unlikely
Note :
Conductor Shape
1.5 - 10 sqmm supplied in non compacted
circular stranded (rm)
16 - 25 sqmm supplied in non compacted
circular stranded (cm) conductor shape
35 - 300 sqmm supplied in non compacted
circular stranded ( rm ) or circular stranded ( cm)
conductor shape
Standard Packing
1.5 - 10 sqmm supplied in coil@ 100 m or
in wooden drum @ 1000 / 2000 m
16 - 300 sqmm supplied in wooden drum
@1000m
CONSTRUCTION DATA
Nominal Cross-sectional area |
Overall Diameter (approx.) |
Cable Weight (approx.) |
mm² | mm | kg/km |
1.5 | 14.0 | 274 |
2.5 | 15.2 | 355 |
4 | 16.6 | 467 |
6 | 18.1 | 598 |
10 | 20.5 | 863 |
16 | 23.4 | 1,2263 |
25 | 27.9 | 1,843 |
35 | 30.9 | 2,475 |
50 | 35.9 | 3,224 |
ELECTRICAL DATA
Nominal Cross-sectional area | Max. DC Conductor Resistance at 20ºC | Max. AC Conductor Resistance at 70ºC |
Max. Current Carrying Capacity at 30 | Inductance | Max. Short circuit current at 1 sec. | |
In Air | In Ground | |||||
mm² | Ω/km | Ω/km | A | A | mH/km | kA |
1.5 | 12.1 | 15.429 | 23 | 29 | 0.315 | 0.21 |
2.5 | 7.41 | 9.449 | 32 | 38 | 0.293 | 0.36 |
4 | 4.61 | 5.878 | 41 | 49 | 0.275 | 0.57 |
6 | 3.08 | 3.927 | 52 | 60 | 0.263 | 0.86 |
10 | 1.83 | 2.334 | 71 | 97 | 0.248 | 1.43 |
16 | 1.153 | 1.466 | 96 | 1088 | 0.238 | 2.29 |
25 | 0.727 | 0.927 | 130 | 141 | 0.240 | 3.58 |
35 | 0.524 | 0.668 | 159 | 170 | 0.233 | 5.01 |
50 | 0.387 | 0.494 | 193 | 201 | 0.232 | 7.15 |