NAYY 1 x ( 10 - 300 ) mm2 0.6/1 kV
AL/PVC/PVC
( Aluminium Conductor, PVC Insulated, PVC Sheathed )
Standard Specification : SNI IEC 60502 - 1
Aplication :
Power cable : Indoors, cable trunking, outdoors and burried in the ground
for power stations, industry and switchgear as well as
for urban supply networks, if mechanical damage is unlikely
Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted
circular stranded (rm)
25 - 300 sqmm supplied in non compacted
or compacted circular stranded (cm)
conductor shape
Standard Packing
10 - 300 sqmm supplied in wooden drum @ 1000 m
CONSTRUCTION DATA
Nominal Cross-sectional area |
Overall Diameter (approx.) |
Cable Weight (approx.) |
mm² | mm | kg/km |
10 | 9.1 | 121 |
16 | 10.1 | 153 |
25 | 11.8 | 211 |
35 | 12.9 | 257 |
50 | 14.7 | 324 |
70 | 16.5 | 411 |
95 | 19.0 | 551 |
120 | 21.0 | 655 |
150 | 22.9 | 793 |
185 | 25.2 | 963 |
240 | 28.5 | 1,222 |
300 | 31.6 | 1,509 |
ELECTRICAL DATA
Nominal Cross-sectional area | Max. DC Conductor Resistance at 20ºC | Max. AC Conductor Resistance at 70ºC |
Max. Current Carrying Capacity at 30 | Inductance | Max. Short circuit current at 1 sec. | |||
In Air | In Ground | |||||||
mm² | Ω/km | Ω/km | A | A | A | A | mH/km | kA |
10 | 3.08 | 3.701 | 49 | 50 | 59 | 58 | 0.396 | 0.76 |
16 | 1.91 | 2.295 | 66 | 68 | 77 | 76 | 0.370 | 1.22 |
25 | 1.20 | 1.442 | 88 | 91 | 98 | 97 | 0.359 | 1.90 |
35 | 0.868 | 1.043 | 109 | 112 | 118 | 117 | 0.344 | 2.66 |
50 | 0.641 | 0.770 | 134 | 138 | 140 | 138 | 0.336 | 3.80 |
70 | 0.443 | 0.533 | 170 | 173 | 171 | 169 | 0.325 | 5.32 |
95 | 0.320 | 0.385 | 210 | 216 | 205 | 202 | 0.320 | 7.22 |
120 | 0.253 | 0.305 | 244 | 251 | 233 | 229 | 0.316 | 9.12 |
150 | 0.206 | 0.249 | 283 | 291 | 261 | 258 | 0.312 | 11.40 |
185 | 0.164 | 0.198 | 328 | 339 | 296 | 292 | 0.310 | 14.05 |
240 | 0.125 | 0.152 | 395 | 407 | 344 | 339 | 0.306 | 18.24 |
300 | 0.100 | 0.122 | 456 | 471 | 388 | 382 | 0.304 | 22.80 |