NAYY 1 x ( 10 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
10 9.1 121
16 10.1 153
25 11.8 211
35 12.9 257
50 14.7 324
70 16.5 411
95 19.0 551
120 21.0 655
150 22.9 793
185 25.2 963
240 28.5 1,222
300 31.6 1,509

 

 
 
 

ELECTRICAL DATA

Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
       
mm² Ω/km Ω/km A A A A mH/km kA
10 3.08 3.701 49 50 59 58 0.396 0.76
16 1.91 2.295 66 68 77 76 0.370 1.22
25 1.20 1.442 88 91 98 97 0.359 1.90
35 0.868 1.043 109 112 118 117 0.344 2.66
50 0.641 0.770 134 138 140 138 0.336 3.80
70 0.443 0.533 170 173 171 169 0.325 5.32
95 0.320 0.385 210 216 205 202 0.320 7.22
120 0.253 0.305 244 251 233 229 0.316 9.12
150 0.206 0.249 283 291 261 258 0.312 11.40
185 0.164 0.198 328 339 296 292 0.310 14.05
240 0.125 0.152 395 407 344 339 0.306 18.24
300 0.100 0.122 456 471 388 382 0.304 22.80