NAYY 2 x ( 10 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
10 18.4 411
16 21.0 536
25 23.5 675
35 26.0 834
50 29.5 954
70 33.0 1,229
95 38.0 1,632
120 41.0 1,926
150 44.0 2,259
185 50.5 2,577
240 55.5 3,576
300 61.5 4,375

 

 
Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
10 3.08 3.701 54 61 0.269 0.76
16 1.91 2.295 73 81 0.253 1.22
25 1.20 1.442 94 103 0.257 1.90
35 0.868 1.043 116 125 0.247 2.66
50 0.641 0.770 141 148 0.247 3.80
70 0.443 0.533 178 183 0.238 5.32
95 0.320 0.385 218 219 0.238 7.22
120 0.253 0.305 253 250 0.233 9.12
150 0.206 0.249 285 279 0.235 11.40
185 0.164 0.198 331 317 0.233 14.05
240 0.125 0.152 390 366 0.232 18.24
300 0.100 0.122 447 413 0.231 22.80