NAYY 2 x ( 10 - 300 ) mm2 0.6/1 kV
AL/PVC/PVC
( Aluminium Conductor, PVC Insulated, PVC Sheathed )
Standard Specification : SNI IEC 60502 - 1
Aplication :
Power cable : Indoors, cable trunking, outdoors and burried in the ground
for power stations, industry and switchgear as well as
for urban supply networks, if mechanical damage is unlikely
Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted
circular stranded (rm)
25 - 300 sqmm supplied in non compacted
or compacted circular stranded (cm)
conductor shape
Standard Packing
10 - 300 sqmm supplied in wooden drum @ 1000 m
CONSTRUCTION DATA
Nominal Cross-sectional area |
Overall Diameter (approx.) |
Cable Weight (approx.) |
mm² | mm | kg/km |
10 | 18.4 | 411 |
16 | 21.0 | 536 |
25 | 23.5 | 675 |
35 | 26.0 | 834 |
50 | 29.5 | 954 |
70 | 33.0 | 1,229 |
95 | 38.0 | 1,632 |
120 | 41.0 | 1,926 |
150 | 44.0 | 2,259 |
185 | 50.5 | 2,577 |
240 | 55.5 | 3,576 |
300 | 61.5 | 4,375 |
Nominal Cross-sectional area | Max. DC Conductor Resistance at 20ºC | Max. AC Conductor Resistance at 70ºC |
Max. Current Carrying Capacity at 30 | Inductance | Max. Short circuit current at 1 sec. | |
In Air | In Ground | |||||
mm² | Ω/km | Ω/km | A | A | mH/km | kA |
10 | 3.08 | 3.701 | 54 | 61 | 0.269 | 0.76 |
16 | 1.91 | 2.295 | 73 | 81 | 0.253 | 1.22 |
25 | 1.20 | 1.442 | 94 | 103 | 0.257 | 1.90 |
35 | 0.868 | 1.043 | 116 | 125 | 0.247 | 2.66 |
50 | 0.641 | 0.770 | 141 | 148 | 0.247 | 3.80 |
70 | 0.443 | 0.533 | 178 | 183 | 0.238 | 5.32 |
95 | 0.320 | 0.385 | 218 | 219 | 0.238 | 7.22 |
120 | 0.253 | 0.305 | 253 | 250 | 0.233 | 9.12 |
150 | 0.206 | 0.249 | 285 | 279 | 0.235 | 11.40 |
185 | 0.164 | 0.198 | 331 | 317 | 0.233 | 14.05 |
240 | 0.125 | 0.152 | 390 | 366 | 0.232 | 18.24 |
300 | 0.100 | 0.122 | 447 | 413 | 0.231 | 22.80 |