NAYY 3 x ( 10 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
10 12.2 213
16 13.5 259
25 14.9 351
35 16.2 422
50 17.9 557
5570 20.5 744
95 23.4 1,066
120 25.0 1,342
150 29.1 1,735
185 33.3 2,331
240 38.1 3,159
300 42.4 3,829

 

 
Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
10 3.08 3.701 46 52 0.269 0.76
16 1.91 2.295 62 69 0.253 1.22
25 1.20 1.442 81 88 0.257 1.90
35 0.868 1.043 100 106 0.247 2.66
50 0.641 0.770 125 131 0.247 3.80
70 0.443 0.533 158 160 0.238 5.32
95 0.320 0.385 194 192 0.238 7.22
120 0.253 0.305 225 219 0.233 9.12
150 0.206 0.249 257 245 0.235 11.40
185 0.164 0.198 297 278 0.233 14.05
240 0.125 0.152 352 322 0.232 18.24
300 0.100 0.122 405 364 0.231 22.80