NAYY 3 x ( 10 - 300 ) mm2 0.6/1 kV

AL/PVC/PVC
( Aluminium Conductor, PVC Insulated, PVC Sheathed )
Standard Specification : SNI IEC 60502 - 1
Aplication :
Power cable : Indoors, cable trunking, outdoors and burried in the ground
for power stations, industry and switchgear as well as
for urban supply networks, if mechanical damage is unlikely
Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted
circular stranded (rm)
25 - 300 sqmm supplied in non compacted
or compacted circular stranded (cm)
conductor shape
Standard Packing
10 - 300 sqmm supplied in wooden drum @ 1000 m
185 - 300 sqmm will be supplied in wooden drum
on available length
CONSTRUCTION DATA
Nominal Cross-sectional area |
Overall Diameter (approx.) |
Cable Weight (approx.) |
mm² | mm | kg/km |
10 | 12.2 | 213 |
16 | 13.5 | 259 |
25 | 14.9 | 351 |
35 | 16.2 | 422 |
50 | 17.9 | 557 |
5570 | 20.5 | 744 |
95 | 23.4 | 1,066 |
120 | 25.0 | 1,342 |
150 | 29.1 | 1,735 |
185 | 33.3 | 2,331 |
240 | 38.1 | 3,159 |
300 | 42.4 | 3,829 |
Nominal Cross-sectional area | Max. DC Conductor Resistance at 20ºC | Max. AC Conductor Resistance at 70ºC |
Max. Current Carrying Capacity at 30 | Inductance | Max. Short circuit current at 1 sec. | |
In Air | In Ground | |||||
mm² | Ω/km | Ω/km | A | A | mH/km | kA |
10 | 3.08 | 3.701 | 46 | 52 | 0.269 | 0.76 |
16 | 1.91 | 2.295 | 62 | 69 | 0.253 | 1.22 |
25 | 1.20 | 1.442 | 81 | 88 | 0.257 | 1.90 |
35 | 0.868 | 1.043 | 100 | 106 | 0.247 | 2.66 |
50 | 0.641 | 0.770 | 125 | 131 | 0.247 | 3.80 |
70 | 0.443 | 0.533 | 158 | 160 | 0.238 | 5.32 |
95 | 0.320 | 0.385 | 194 | 192 | 0.238 | 7.22 |
120 | 0.253 | 0.305 | 225 | 219 | 0.233 | 9.12 |
150 | 0.206 | 0.249 | 257 | 245 | 0.235 | 11.40 |
185 | 0.164 | 0.198 | 297 | 278 | 0.233 | 14.05 |
240 | 0.125 | 0.152 | 352 | 322 | 0.232 | 18.24 |
300 | 0.100 | 0.122 | 405 | 364 | 0.231 | 22.80 |