NAYY 4 x ( 10 - 300 ) mm2 0.6/1 kV
AL/PVC/PVC
( Aluminium Conductor, PVC Insulated, PVC Sheathed )
Standard Specification : SNI IEC 60502 - 1
Aplication :
Power cable : Indoors, cable trunking, outdoors and burried in the ground
for power stations, industry and switchgear as well as
for urban supply networks, if mechanical damage is unlikely
Note :
Conductor Shape
10 - 16 sqmm supplied in non compacted
circular stranded (rm)
25 - 35 sqmm supplied in non compacted
or compacted circular stranded (cm)
50 - 300 sqmm supplied in Sector shaped stranded (sm)
Standard Packing
10 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be supplied in wooden drum
on available length
CONSTRUCTION DATA
Nominal Cross-sectional area |
Overall Diameter (approx.) |
Cable Weight (approx.) |
mm² | mm | kg/km |
10 | 21.5 | 541 |
16 | 24.5 | 715 |
25 | 27.0 | 920 |
35 | 30.0 | 1,147 |
50 | 35.5 | 1,306 |
5570 | 39.0 | 1,659 |
95 | 44.5 | 2,163 |
120 | 48.5 | 2,599 |
150 | 54.5 | 3,164 |
185 | 59.0 | 3,867 |
240 | 66.0 | 4,854 |
300 | 72.5 | 5,884 |
Nominal Cross-sectional area | Max. DC Conductor Resistance at 20ºC | Max. AC Conductor Resistance at 70ºC |
Max. Current Carrying Capacity at 30 | Inductance | Max. Short circuit current at 1 sec. | |
In Air | In Ground | |||||
mm² | Ω/km | Ω/km | A | A | mH/km | kA |
10 | 3.08 | 3.701 | 53 | 59 | 0.269 | 0.76 |
16 | 1.91 | 2.295 | 71 | 77 | 0.253 | 1.22 |
25 | 1.20 | 1.442 | 93 | 99 | 0.257 | 1.90 |
35 | 0.868 | 1.043 | 115 | 199 | 0.247 | 2.66 |
50 | 0.641 | 0.770 | 134 | 135 | 0.247 | 3.80 |
70 | 0.443 | 0.533 | 167 | 165 | 0.238 | 5.32 |
95 | 0.320 | 0.385 | 207 | 198 | 0.238 | 7.22 |
120 | 0.253 | 0.305 | 240 | 225 | 0.233 | 9.12 |
150 | 0.206 | 0.249 | 277 | 254 | 0.235 | 11.40 |
185 | 0.164 | 0.198 | 316 | 286 | 0.233 | 14.05 |
240 | 0.125 | 0.152 | 377 | 332 | 0.232 | 18.24 |
300 | 0.100 | 0.122 | 433 | 376 | 0.231 | 22.80 |