NYAF 1.5 - 300 mm² 450 / 750 V
Cu/PVC-f
( Flexible Copper Conductor, PVC Insulated )
Standard Specification : SNI 04-6629-5
Aplication :
Power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, distribution panels, luminaires and
other electrical used in dry indoor premises.
Note :
Conductor Shape
Annealed plain copper wires bunch stranded
Flexible bunched wire
Standard Packing
1.5 - 16 sqmm supplied in coil@ 100 m
25 - 300 sqmm supplied in wooden drum
@ 1000 m
CONSTRUCTION AND ELECTRICAL DATA
Conductor | Nominal Thickness insulation | Overall Diameter (approx.) | Cable Weight (approx.) | Min. Insulation DC Resistance at |
Max. Current Carrying Capacity at 30⁰c |
Max. Short circuit current at 1 sec | ||
Nominal Cross-sectional | Nominal of wire and diameter | In air | In Pipe | |||||
mm² | mm | mm | mm | kg/km | A | A | mH/km | kA |
0.5 f | 16/0.2 | 0.6 | 2.6 | 10 | 50 | 2.5 | - | 0.06 |
0.75 f | 24/0.2 | 0.6 | 2.8 | 13 | 50 | 7 | - | 0.09 |
1.0 f | 32/0.2 | 0.6 | 3.0 | 16 | 50 | 11 | 19 | 0.120 |
1.5 f | 30/0.25 | 0.7 | 3.5 | 23 | 50 | 15 | 24 | 0.17 |
2.5 f | 50//0.25 | 0.8 | 4.2 | 36 | 50 | 20 | 32 | 0.29 |
4 f | 56//0.3 | 0.8 | 5.0 | 51 | 50 | 25 | 41 | 0.46 |
6 f | 84/0.3 | 0.8 | 6.3 | 73 | 50 | 33 | 53 | 0.69 |
10 f | 84/0.4 | 1.0 | 7.4 | 116 | 50 | 45 | 72 | 1.15 |
16 f | 126/0.4 | 1.0 | 8.6 | 180 | 40 | 61 | 97 | 1.84 |
25 f | 196/0.4 | 1.2 | 10.8 | 275 | 40 | 82 | 128 | 2.88 |
35 f | 278/0.4 | 1.2 | 12.0 | 385 | 40 | 102 | 156 | 4.03 |
50 f | 398//0.4 | 1.4 | 14.5 | 550 | 40 | 131 | 195 | 5.75 |
70 f | 360//0.5 | 1.4 | 16.5 | 750 | 30 | 164 | 243 | 8.05 |
95 f | 475/0.5 | 1.6 | 19.5 | 1000 | 30 | 205 | 287 | 10.93 |
120 f | 608/0.5 | 1.6 | 21.0 | 1240 | 30 | 233 | 342 | 13.80 |
150 f | 760/0.5 | 1.8 | 23.5 | 1550 | 30 | - | 386 | 17.25 |
185 f | 925/0.5 | 2.0 | 26.0 | 1900 | 20 | - | 441 | 21.28 |
240 f | 1221//0.5 | 2.2 | 29.5 | 2450 | 20 | - | 525 | 27.60 |