NYB(CU)Y 1 x ( 16 - 300 ) mm2 0.6/1 kV
CU/PVC/DSTA/PVC
( Copper Conductor, PVC Insulated, Double Galvanis Tape Armoured, PVC Sheathed )
Standard Specification : SNI IEC 60502 - 1
Aplication :
Power cable : Indoors, cable trunking, outdoors and burried in the ground
for power stations, industry and switchgear as well as
for urban supply networks, if mechanical damage is unlikely
Note :
Conductor Shape
16 sqmm supplied in non compacted circular stranded (rm)
35 - 300 sqmm supplied in non compacted
circular stranded ( rm ) or circular stranded ( cm)
conductor shape
Standard Packing
35 - 300 sqmm supplied in wooden drum
@1000m
CONSTRUCTION DATA
Nominal Cross-sectional area |
Overall Diameter (approx.) |
Cable Weight (approx.) |
mm² | mm | kg/km |
16 | 15.4 | 396 |
25 | 16.2 | 497 |
35 | 17.3 | 608 |
50 | 19.3 | 785 |
70 | 21.5 | 1,011 |
95 | 23.5 | 1,298 |
120 | 25.0 | 1,552 |
150 | 27.0 | 1,850 |
185 | 29.5 | 2,279 |
240 | 32.5 | 2,926 |
300 | 35.5 | 3,521 |
ELECTRICAL DATA
Nominal Cross-sectional area | Max. DC Conductor Resistance at 20ºC | Max. AC Conductor Resistance at 70ºC |
Max. Current Carrying Capacity at 30 | Inductance | Max. Short circuit current at 1 sec. | |||
In Air | In Ground | |||||||
mm² | Ω/km | Ω/km | A | A | A | A | mH/km | kA |
16 | 0.150 | 1.376 | 94 | 97 | 98 | 101 | 0.345 | 1.84 |
25 | 0.727 | 0.870 | 124 | 127 | 127 | 131 | 0.336 | 2.88 |
35 | 0.254 | 0.627 | 174 | 169 | 249 | 183 | 0.345 | 4.03 |
50 | 0.387 | 0.464 | 212 | 206 | 296 | 216 | 0.336 | 5.75 |
70 | 0.268 | 0.321 | 269 | 261 | 365 | 265 | 0.326 | 8.05 |
95 | 0.193 | 0.232 | 331 | 321 | 438 | 316 | 0.321 | 10.93 |
120 | 0.1530 | 0.184 | 386 | 374 | 499 | 359 | 0.316 | 13.80 |
150 | 0.1240 | 0.150 | 442 | 428 | 561 | 402 | 0.313 | 17.25 |
185 | 0.0991 | 0.121 | 511 | 494 | 637 | 454 | 0.310 | 21.28 |
240 | 0.075 | 0.093 | 612 | 590 | 743 | 527 | 0.307 | 27.60 |
300 | 0.0601 | 0.075 | 707 | 678 | 843 | 544 | 0.305 | 34.50 |