NYB(AL)Y 2 x ( 16 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
16 15.4 396
25 16.2 497
35 17.3 608
50 19.3 785
70 21.5 1,011
95 23.5 1,298
120 25.0 1,552
150 27.0 1,850
185 29.5 2,279
240 32.5 2,926
300 35.5 3,521

 

ELECTRICAL DATA

Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 23 27 0.340 0.17
2.5 7.41 8.866 31 36 0.304 0.29
4 4.61 5.516 41 48 0.303 0.46
6 3.08 3.685 52 60 0.288 0.69
10 1.83 2.190 71 81 0.269 1.15
16 1.153 1.378 94 105 0.256 1.84
25 0.727 0.870 124 135 0.255 2.88
35 0.524 0.627 152 163 0.246 4.03
50 0.387 0.464 184 193 0.247 5.75
70 0.268 0.321 232 238 0.238 8.05
95 0.193 0.132 282 283 0.233 10.93
120 0.153 0.184 330 324 0.233 13.80
150 0.124 0.150 376 363 0.233 17.25
185 0.0991 0.121 430 408 0.233 21.28
240 0.0754 0.093 506 472 0.232 27.60
300 0.0601 0.075 576 528 0.231 34.50