NYB(AL)Y 3 x ( 16 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 14.1 308
2.5 15.1 335
4 17.1 442
6 18.3 534
10 20.2 719
16 22.5 958
25 26.1 1,336
35 28.7 1,701
50 33.1 1,999
70 37.1 2,700
95 42.4 3,974
120 46.7 4,739
150 51.1 5,765
185 56.6 7,048
240 63.6 9,015
300 70.3 10,964

 

 
 

ELECTRICAL DATA

Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 20 23 0.340 0.17
2.5 7.41 8.866 26 31 0.304 0.29
4 4.61 5.516 35 41 0.303 0.46
6 3.08 3.685 44 51 0.288 0.69
10 1.83 2.190 61 69 0.269 1.15
16 1.153 1.378 80 89 0.256 1.84
25 0.727 0.870 106 115 0.255 2.88
35 0.524 0.627 131 138 0.246 4.03
50 0.387 0.464 164 170 0.247 5.75
70 0.268 0.321 205 207 0.238 8.05
95 0.193 0.132 255 249 0.233 10.93
120 0.153 0.184 294 284 0.233 13.80
150 0.124 0.150 336 317 0.233 17.25
185 0.0991 0.121 386 358 0.233 21.28
240 0.0754 0.093 455 413 0.232 27.60
300 0.0601 0.075 522 465 0.231 34.50