NYB(CU)Y 4 x ( 16 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 14.4 317
2.5 15.2 379
4 17.5 518
6 18.9 633
10 21.5 873
16 24.0 1,170
25 27.5 1,658
35 30.5 2,126
50 36.0 2,632
70 40.5 3,870
95 46.0 5,125
120 50.0 6,190
150 56.5 7,563
185 60.5 9,199
240 68.0 11,751
300 74.0 14, 348

 

 
 

ELECTRICAL DATA

Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 22 27 0.340 0.17
2.5 7.41 8.866 30 36 0.304 0.29
4 4.61 5.516 40 47 0.303 0.46
6 3.08 3.685 51 58 0.288 0.69
10 1.83 2.190 69 78 0.269 1.15
16 1.153 1.378 92 100 0.256 1.84
25 0.727 0.870 123 130 0.255 2.88
35 0.524 0.627 151 156 0.246 4.03
50 0.387 0.464 174 175 0.247 5.75
70 0.268 0.321 220 215 0.238 8.05
95 0.193 0.132 271 257 0.233 10.93
120 0.153 0.184 313 292 0.233 13.80
150 0.124 0.150 362 329 0.233 17.25
185 0.0991 0.121 411 369 0.233 21.28
240 0.0754 0.093 487 427 0.232 27.60
300 0.0601 0.075 557 480 0.231 34.50