NYB(CU)Y 5 x ( 16 - 300 ) mm2 0.6/1 kV
CU/PVC/DSTA-PVC
( Copper Conductor, PVC Insulated, Double Galvanis Tape Armoured, PVC Sheathed )
Standard Specification : SNI IEC 60502 - 1
Aplication :
Power cable : Indoors, cable trunking, outdoors and burried in the ground
for power stations, industry and switchgear as well as
for urban supply networks, if mechanical damage is unlikely
Note :
Conductor Shape
1.5 - 10 sqmm supplied in Solid ( re )
or non compacted circular stranded (rm)
16 - 25 sqmm supplied in non compacted
circular stranded ( rm ) conductor shape
35 - 300 sqmm supplied in non compacted
circular stranded ( rm ) or circular stranded ( cm)
conductor shape
Standard Packing
1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm supplied in wooden drum
on available length.
CONSTRUCTION DATA
Nominal Cross-sectional area |
Overall Diameter (approx.) |
Cable Weight (approx.) |
mm² | mm | kg/km |
1.5 | 15.0 | 357 |
2.5 | 16.3 | 443 |
4 | 18.9 | 612 |
6 | 20.5 | 754 |
10 | 23.5 | 1,041 |
16 | 26.0 | 1,406 |
25 | 30.0 | 2,006 |
35 | 33.5 | 2,599 |
50 | 38.5 | 3,342 |
70 | 40.5 | 3,870 |
95 | 46.0 | 5,125 |
120 | 50.0 | 6,190 |
150 | 56.5 | 7,563 |
185 | 60.5 | 9,199 |
240 | 68.0 | 11,751 |
300 | 74.0 | 14, 348 |
ELECTRICAL DATA
Nominal Cross-sectional area | Max. DC Conductor Resistance at 20ºC | Max. AC Conductor Resistance at 70ºC |
Max. Current Carrying Capacity at 30 | Inductance | Max. Short circuit current at 1 sec. | |
In Air | In Ground | |||||
mm² | Ω/km | Ω/km | A | A | mH/km | kA |
1.5 | 12.1 | 14.478 | 23 | 28 | 0.340 | 0.17 |
2.5 | 7.41 | 8.866 | 31 | 36 | 0.304 | 0.29 |
4 | 4.61 | 5.516 | 42 | 48 | 0.303 | 0.46 |
6 | 3.08 | 3.685 | 53 | 59 | 0.288 | 0.69 |
10 | 1.83 | 2.190 | 72 | 79 | 0.269 | 1.15 |
16 | 1.153 | 1.378 | 95 | 102 | 0.256 | 1.84 |
25 | 0.727 | 0.870 | 128 | 132 | 0.255 | 2.88 |
35 | 0.524 | 0.627 | 157 | 158 | 0.246 | 4.03 |
50 | 0.387 | 0.464 | 191 | 186 | 0.247 | 5.75 |