NYM 2 x ( 1.5 - 35 ) mm2 300 / 500 V

Cu/PVC
(Copper Conductor, PVC Insulated)
Standard Specification : SNI 04-6629; IEC 60227-3
Aplication :
For building installed in conduit in dry locationa
and interwiring in switch board and control panel.
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re)
or non compacted circular stranded (rm)
Conductor Shape
16 - 35 sqmm supplied in non compacted
circular stranded ( rm ) conductor shape
Standard Packing
1.5 - 10 sqmm supplied in coil@ 100 m or
in wooden drum @ 1000 / 2000 m
16 - 35 sqmm supplied in wooden drum
@ 1000 m
CONSTRUCTION DATA
Nominal Cross-sectional area |
Overall Diameter (approx.) |
Cable Weight (approx.) |
mm² | mm | kg/km |
1.5 | 9.5 | 116 |
2.5 | 10.5 | 157 |
4 | 11.5 | 203 |
6 | 12.5 | 262 |
10 | 16.0 | 426 |
16 | 19.0 | 638 |
25 | 23.0 | 962 |
35 | 26.0 | 1,270 |
ELECTRICAL DATA
Nominal Cross sectional area |
Max. DC Conductor Resistance at 20ºC | Max. AC Conductor Resistance at 70ºC |
Min Insulation Resistance at 70ºC |
Max. Current In Air |
In Pipe |
Inductance | Max. Short circuit current at 1 sec. |
mm² | Ω/km | Ω/km | Ω.kmM. | A | A | mH/km | kA |
1.5 | 12.1 | 14.478 | 0.010 | 19 | 16 | 0.329 | 0.17 |
2.5 | 7.41 | 8.866 | 0.0090 | 25 | 22 | 0.32 | 0.29 |
4 | 4.61 | 5.516 | 0.0077 | 34 | 30 | 0.297 | 0.460 |
6 | 3.08 | 3.685 | 0.0065 | 44 | 39 | 0.281 | 0.69 |
10 | 1.83 | 2.190 | 0.0065 | 61 | 53 | 0.278 | 1.15 |
16 | 1.15 | 1.378 | 0.0050 | 51 | 96 | 1.38 | 1.84 |
25 | 0.727 | 0.870 | 0.0050 | 108 | 94 | 0.252 | 2.88 |
35 | 0.524 | 0.627 | 0.0040 | 134 | 117 | 0.244 | 4.03 |