NYM 4 x ( 1.5 - 35 ) mm2 300 / 500 V

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 10.5 169
2.5 12.0 230
4 13.6 338
6 15.5 446
10 18.3 638
16 22.5 1,027
25 27.5 1,579
35 30.0 2,014

ELECTRICAL DATA

Nominal Cross
sectional area
Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Min Insulation
Resistance at 70ºC

Max. Current
Carrying Capacity at 30ºC

In Air

 

 

In Pipe

Inductance Max. Short circuit current at 1 sec.
mm² Ω/km Ω/km Ω.kmM. A A mH/km kA
1.5 12.1 14.478 0.010 19 16 0.329 0.17
2.5 7.41 8.866 0.0090 25 22 0.32 0.29
4 4.61 5.516 0.0077 34 30 0.297 0.460
6 3.08 3.685 0.0065 44 39 0.281 0.69
10 1.83 2.190 0.0065 61 53 0.278 1.15
16 1.15 1.378 0.0050 82 72 0.255 1.84
25 0.727 0.870 0.0050 108 94 0.252 2.88
35 0.524 0.627 0.0040 134 127 0.244 4.03