CU/PVC/PVC-f (NYMHY) 300 / 500 Volt

( Flexible Copper Conductor, PVC Insulated )
Standard Specification : SNI 04-6629-5

 

Aplication :
 Power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, distribution panels, luminaires and
other electrical used in dry indoor premises.

Note :
Conductor Shape

Annealed plain copper wires bunch stranded
Flexible bunched wire

Standard Packing
1.5 - 16 sqmm supplied in coil@ 100 m
25 - 300 sqmm supplied in wooden drum
@ 1000 m

CONSTRUCTION AND ELECTRICAL DATA

Conductor Nominal Thickness Overall Diameter (approx.) Cable Weight (approx.) Min. Insulation DC.Resistance at 20ºC Max. Current Carrying Capacity in Air Max. Short circuit current  at 1 sec.
Nominal No.of wire and diameter Insulation Outer Sheath 30ºC 40ºC
mm² mm mm mm   kg/km A A mH/km kA
2 x 0.5 f 16/0.2 0.6 0.8 6.0 56 40 2 1.8 0.06
2 x 0.75 f 24/0.2 0.6 0.8 6.5 56 40 6 5.5 0.09
2 x 1.0 f 32/0.2 0.6 0.8 6.7 66 40 10 9.2 0.120
2 x 1.5 f 30/0.25 0.7 0.9 7.7 90 40 15 13.8 0.17
2 x 2.5 f 50//0.25 0.8 1.0 9.4 140 40 20 18.4 0.29
2 x 4 f 56//0.3 0.8 1.0 11.3 209 40 27.5 25.3 0.46
3 x 0.5 f 16/0.2 0.8 0.8 6.4 60 40 2 1.8 0.06
3 x 0.75 f 24/0.2 1.0 0.8 6.8 77 40 6 5.5 0.09
3 x 1.0 f 32/0.2 1.0 0.8 7.1 90 40 10 9.2 0.120
3 x 1.5 f 30/0.25 1.2 0.9 8.3 147 40 15 13.8 0.17
3 x 2.5 f 50//0.25 1.2 1.0 10.2 190 40 20 18.4 0.29
3 x 4 f 56//0.3 1.4 1.0 12.0 265 40 27.5 25.3 0.46
4 x 0.5 f 16/0.2 0.6 0.8 7.0 70 40 2 1.8 0.06
4 x 0.75 f 24/0.2 0.6 0.8 7.4 96 40 6 5.5 0.09
4 x 1.0 f 32/0.2 0.6 0.8 8.0 121 40 10 9.2 0.120
4 x 1.5 f 30/0.25 0.7 0.9 9.1 167 40 15 13.8 0.17
4 x 2.5 f 50//0.25 0.8 1.0 11.2 237 40 20 18.4 0.29
4 x 4 f 56//0.3 0.8 1.0 13.1 330 40 27.5 25.3 0.46
4 x 0.5 f 16/0.2 0.6 0.8 7.8 90 40 2 1.8 0.06
4 x 0.75 f 24/0.2 0.6 0.8 8.3 116 40 6 5.5 0.09
4 x 1.0 f 32/0.2 0.6 0.8 8.7 139 40 10 9.2 0.120
4 x 1.5 f 30/0.25 0.7 0.9 10.3 194 40 15 13.8 0.17
4 x 2.5 f 50//0.25 0.8 1.0 12.4 291 40 20 18.4 0.29
4 x 4 f 56//0.3 0.8 1.0 14.3 391 40 27.5 25.3 0.46