NYY 2 x ( 1.5 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 12.2 213
2.5 13.5 259
4 14.9 351
6 16.2 422
10 17.9 557
16 20.5 744
25 23.4 1,066
35 25.0 1,342
50 29.1 1,735
70 33.3 2,331
95 38.1 3,159
120 42.4 3,829
150 46.2 4,467
185 50.8 5,805
240 57.9 7,480
300 64.3 9,250
 
 
 
Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 21 27 0.328 0.17
2.5 7.41 8.866 29 36 0.304 0.29
4 4.61 5.516 38 47 0.303 0.46
6 3.08 3.685 48 59 0.288 0.69
10 1.83 2.190 66 78 0.269 1.15
16 1.15 1.378 90 102 0.256 1.84
25 0.727 0.870 120 134 0.255 2.88
35 0.524 0.627 150 160 0.246 4.03
50 0.387 0.464 180 187 0.247 5.75
70 0.268 0.321 230 230 0.238 8.05
95 0.193 0.132 275 280 0.238 10.93
120 0.153 0.184 320 320 0.233 13.80
150 0.124 0.150 379 355 0.233 17.25
185 0.0991 0.121 430 409 0.233 21.28
240 0.0754 0.093 510 472 0.232 27.60
300 0.0601 0.075 590 525 0.231 34.50