NYY 3 x ( 1.5 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 12.7 237
2.5 13.7 295
4 15.7 406
6 16.9 495
10 18.9 669
16 21.1 912
25 24.8 1,325
35 27.2 1,688
50 30.0 1,829
70 34.0 2,527
95 38.5 3,404
120 41.5 4,155
150 46.0 5,119
185 50.5 6,324
240 57.5 8,224
300 62.5 10,304
 
 
 
Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 19 23 0.328 0.17
2.5 7.41 8.866 26 31 0.304 0.29
4 4.61 5.516 34 40 0.303 0.46
6 3.08 3.685 44 50 0.288 0.69
10 1.83 2.190 60 69 0.269 1.15
16 1.15 1.378 79 88 0.256 1.84
25 0.727 0.870 105 116 0.255 2.88
35 0.524 0.627 130 138 0.246 4.03
50 0.387 0.464 160 165 0.247 5.75
70 0.268 0.321 200 205 0.238 8.05
95 0.193 0.132 250 247 0.238 10.93
120 0.153 0.184 289 281 0.233 13.80
150 0.124 0.150 325 315 0.233 17.25
185 0.0991 0.121 370 355 0.233 21.28
240 0.0754 0.093 435 415 0.232 27.60
300 0.0601 0.075 517 464 0.231 34.50