NYY 4 x ( 1.5 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 13.6 237
2.5 14.7 295
4 16.9 406
6 18.2 495
10 20.4 669
16 22.9 912
25 27.5 1,325
35 30.0 1,688
50 34.1 1,829
70 38.1 2,527
95 44.5 3,404
120 48.5 4,155
150 51.8 5,119
185 59.0 6,324
240 66.0 8,224
300 72.5 10,304
 
 
 
Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 22 27 0.328 0.17
2.5 7.41 8.866 29 35 0.304 0.29
4 4.61 5.516 39 46 0.303 0.46
6 3.08 3.685 50 57 0.288 0.69
10 1.83 2.190 68 77 0.269 1.15
16 1.15 1.378 90 99 0.256 1.84
25 0.727 0.870 121 128 0.255 2.88
35 0.524 0.627 149 154 0.246 4.03
50 0.387 0.464 173 173 0.247 5.75
70 0.268 0.321 215 212 0.238 8.05
95 0.193 0.132 266 255 0.238 10.93
120 0.153 0.184 308 289 0.233 13.80
150 0.124 0.150 357 327 0.233 17.25
185 0.0991 0.121 405 366 0.233 21.28
240 0.0754 0.093 482 425 0.232 27.60
300 0.0601 0.075 552 479 0.231 34.50