NYY 5 x ( 1.5 - 300 ) mm2 0.6/1 kV

CONSTRUCTION DATA

Nominal Cross-sectional area

Overall Diameter (approx.)

Cable Weight (approx.)

mm² mm kg/km
1.5 14.8 302
2.5 16.0 382
4 18.7 541
6 20.5 677
10 23.0 954
16 26.0 1,309
25 30.0 1,895
35 33.0 2,478
50 38.0 3,161
Nominal Cross-sectional area Max. DC Conductor Resistance at 20ºC Max. AC Conductor
Resistance at 70ºC
Max. Current Carrying Capacity at 30 Inductance Max. Short circuit current at 1 sec.
In Air In Ground
mm² Ω/km Ω/km A A mH/km kA
1.5 12.1 14.478 23 27 0.328 0.17
2.5 7.41 8.866 30 36 0.304 0.29
4 4.61 5.516 41 47 0.303 0.46
6 3.08 3.685 52 52 0.288 0.69
10 1.83 2.190 71 78 0.269 1.15
16 1.15 1.378 94 101 0.256 1.84
25 0.727 0.870 128 131 0.255 2.88
35 0.524 0.627 155 157 0.246 4.03
50 0.387 0.464 189 185 0.247 5.75