NYY 5 x ( 1.5 - 300 ) mm2 0.6/1 kV

Cu/PVC
( Copper Conductor, PVC Insulated, PVC Sheathed )
Standard Specification : SNI 04-6629; IEC 60227-3
Aplication :
Power cable : Indoors, cable trunking, outdoors and burried in the ground
for power stations, industry and switchgear as well as
for urban supply networks, if mechanical damage is unlikely
Note :
Conductor Shape
1.5 - 10 sqmm supplied in Solid ( re )
or non compacted circular stranded (rm)
16 sqmm supplied in non compacted
circular stranded ( rm ) conductor shape
25 - 50 sqmm supplied in non compacted
circular stranded ( rm ) or circular stranded ( cm)
conductor shape
Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
CONSTRUCTION DATA
Nominal Cross-sectional area |
Overall Diameter (approx.) |
Cable Weight (approx.) |
mm² | mm | kg/km |
1.5 | 14.8 | 302 |
2.5 | 16.0 | 382 |
4 | 18.7 | 541 |
6 | 20.5 | 677 |
10 | 23.0 | 954 |
16 | 26.0 | 1,309 |
25 | 30.0 | 1,895 |
35 | 33.0 | 2,478 |
50 | 38.0 | 3,161 |
Nominal Cross-sectional area | Max. DC Conductor Resistance at 20ºC | Max. AC Conductor Resistance at 70ºC |
Max. Current Carrying Capacity at 30 | Inductance | Max. Short circuit current at 1 sec. | |
In Air | In Ground | |||||
mm² | Ω/km | Ω/km | A | A | mH/km | kA |
1.5 | 12.1 | 14.478 | 23 | 27 | 0.328 | 0.17 |
2.5 | 7.41 | 8.866 | 30 | 36 | 0.304 | 0.29 |
4 | 4.61 | 5.516 | 41 | 47 | 0.303 | 0.46 |
6 | 3.08 | 3.685 | 52 | 52 | 0.288 | 0.69 |
10 | 1.83 | 2.190 | 71 | 78 | 0.269 | 1.15 |
16 | 1.15 | 1.378 | 94 | 101 | 0.256 | 1.84 |
25 | 0.727 | 0.870 | 128 | 131 | 0.255 | 2.88 |
35 | 0.524 | 0.627 | 155 | 157 | 0.246 | 4.03 |
50 | 0.387 | 0.464 | 189 | 185 | 0.247 | 5.75 |