NYYHY 1.5-300mm20.6/1kV

CU/PVC/PVC-f
( Flexible Copper Conductor, PVC Insulated, PVC Sheath )
Standard Specification : SNI IEC 60502-1

Aplication :
Power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, distribution panels, luminaires and
other electrical used in dry indoor premises and Outdoor application.

Note :
Conductor Shape

Annealed plain copper wires bunch stranded
Flexible bunched wire

Standard Packing
1.5 - 16 sqmm supplied in coil@ 100 m
25 - 300 sqmm supplied in wooden drum
@ 1000 m

CONSTRUCTION AND ELECTRICAL DATA

Conductor Nominal Thickness Insulation Overall Diameter (approx.) Cable Weight (approx.) Min. Insulation DC.Resistance at 20ºC Max. Current Carrying Capacity at 30ºC Max. Short circuit current  at 1 sec.
Nominal Cross-sectional area No.of wire and diameter In Air
mm² mm mm mm kg/km A A kA
1 x 1.5 44/0.2 0.7 6.0 57 50 18 0.17
1 x 2.5 74/0.2 0.8 6.5 41 50 23 0.29
1 x 4 30/0.4 0.8 7.4 98 50 31 0.46
1 x 6 44/0.4 0.8 8.0 121 50 40 0.69
1 x 10 74/0.4 1.0 8.9 167 50 54 1.15
1 x 16 120/0.4 1.0 10.0 233 40 61 1.84
1 x 25 185/0.4 1.2 11.6 335 40 80 2.88
1 x 35 259/0.4 1.2 12.7 434 40 116 4.03
1 x 50 370/0.4 1.4 14.6 596 40 146 5.75
1 x 70 518/0.4 1.4 16.4 797 30 184 8.05
1 x 95 703/0.4 1.6 18.5 1053 30 221 10.93
1 x 120 923/0.4 1.6 20.5 1344 30 259 13.80
1 x 150 1162/0.4 1.8 22.8 1680 30 301 17.25
1 x 185 1416/0.4 2.0 24.9 2026 20 343 21.28
1 x 240 1839/0.4 2.2 27.9 2598 20 412 27.60
1 x 300 1342/0.5 2.4 29.8 2966 20 475 34.50