NYYHY 1.5-300 mm² 0.6/1kV

CU/PVC/PVC-f
( Flexible Copper Conductor, PVC Insulated, PVC Sheath )
Standard Specification : SNI IEC 60502-1

Aplication :
Power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, distribution panels, luminaires and
other electrical used in dry indoor premises and Outdoor application.

Note :
Conductor Shape

Annealed plain copper wires bunch stranded
Flexible bunched wire

Standard Packing
1.5 - 16 sqmm supplied in coil@ 100 m
25 - 300 sqmm supplied in wooden drum
@ 1000 m

CONSTRUCTION AND ELECTRICAL DATA

Conductor Nominal Thickness Insulation Overall Diameter (approx.) Cable Weight (approx.) Min. Insulation DC.Resistance at 20ºC Max. Current Carrying Capacity at 30ºC Max. Short circuit current  at 1 sec.
Nominal Cross-sectional area No.of wire and diameter In Air
mm² mm mm mm kg/km A A kA
3 x 1.5 44/0.2 0.7 10.0 156 50 15 0.17
3 x 2.5 74/0.2 0.8 11.5 210 50 20 0.29
3 x 4 30/0.4 0.8 12.6 268 50 25 0.46
3 x 6 44/0.4 0.8 13.9 339 50 30 0.69
3 x 10 74/0.4 1.0 16.7 504 50 41 1.15
3 x 16 120/0.4 1.0 19.0 703 40 58 1.84
3 x 25 185/0.4 1.2 22.5 1014 40 78 2.88
3 x 35 259/0.4 1.2 24.9 1317 40 107 4.03
3 x 50 370/0.4 1.4 29.4 1845 40 135 5.75
3 x 70 518/0.4 1.4 33.0 2446 30 170 8.05
3 x 95 703/0.4 1.6 37.8 3255 30 202 10.93
3 x 120 923/0.4 1.6 42.1 4158 30 237 13.80
3 x 150 1162/0.4 1.8 46.8 5175 30 273 17.25
3 x 185 1416/0.4 2.0 51.7 6290 20 309 21.28
3 x 240 1839/0.4 2.2 58.2 8071 20 366 27.60
3 x 300 1342/0.5 2.4 62.0 9176 20 418 34.50