NYYHY 1.5-300 mm² 0.6/1kV

CU/PVC/PVC-f
( Flexible Copper Conductor, PVC Insulated, PVC Sheath )
Standard Specification : SNI IEC 60502-1

Aplication :
Power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, distribution panels, luminaires and
other electrical used in dry indoor premises and Outdoor application.

Note :
Conductor Shape

Annealed plain copper wires bunch stranded
Flexible bunched wire

Standard Packing
1.5 - 16 sqmm supplied in coil@ 100 m
25 - 300 sqmm supplied in wooden drum
@ 1000 m

CONSTRUCTION AND ELECTRICAL DATA

Conductor Nominal Thickness Insulation Overall Diameter (approx.) Cable Weight (approx.) Min. Insulation DC.Resistance at 20ºC Max. Current Carrying Capacity at 30ºC Max. Short circuit current  at 1 sec.
Nominal Cross-sectional area No.of wire and diameter In Air
mm² mm mm mm kg/km A A kA
4 x 1.5 44/0.2 0.7 10.7 184 50 15 0.17
4 x 2.5 74/0.2 0.8 12.4 253 50 20 0.29
4 x 4 30/0.4 0.8 13.6 327 50 25 0.46
4 x 6 44/0.4 0.8 15.0 416 50 30 0.69
4 x 10 74/0.4 1.0 18.2 632 50 41 1.15
4 x 16 120/0.4 1.0 20.8 893 40 58 1.84
4 x 25 185/0.4 1.2 24.7 1299 40 78 2.88
4 x 35 259/0.4 1.2 27.6 1714 40 99 4.03
4 x 50 370/0.4 1.4 32.5 2397 40 124 5.75
4 x 70 518/0.4 1.4 36.6 3195 30 156 8.05
4 x 95 703/0.4 1.6 42.1 4280 30 186 10.93
4 x 120 923/0.4 1.6 46.6 5432 30 218 13.80
4 x 150 1162/0.4 1.8 52.1 6810 30 251 17.25
4 x 185 1416/0.4 2.0 57.6 8286 20 285 21.28
4 x 240 1839/0.4 2.2 64.7 10613 20 338 27.60
4 x 300 1342/0.5 2.4 69.2 12124 20 387 34.50