NYYHY 1.5-300 mm² 0.6/1kV
CU/PVC/PVC-f
( Flexible Copper Conductor, PVC Insulated, PVC Sheath )
Standard Specification : SNI IEC 60502-1
Aplication :
Power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, distribution panels, luminaires and
other electrical used in dry indoor premises and Outdoor application.
Note :
Conductor Shape
Annealed plain copper wires bunch stranded
Flexible bunched wire
Standard Packing
1.5 - 16 sqmm supplied in coil@ 100 m
25 - 300 sqmm supplied in wooden drum
@ 1000 m
CONSTRUCTION AND ELECTRICAL DATA
Conductor | Nominal Thickness Insulation | Overall Diameter (approx.) | Cable Weight (approx.) | Min. Insulation DC.Resistance at 20ºC | Max. Current Carrying Capacity at 30ºC | Max. Short circuit current at 1 sec. | |
Nominal Cross-sectional area | No.of wire and diameter | In Air | |||||
mm² | mm | mm | mm | kg/km | A | A | kA |
4 x 1.5 | 44/0.2 | 0.7 | 10.7 | 184 | 50 | 15 | 0.17 |
4 x 2.5 | 74/0.2 | 0.8 | 12.4 | 253 | 50 | 20 | 0.29 |
4 x 4 | 30/0.4 | 0.8 | 13.6 | 327 | 50 | 25 | 0.46 |
4 x 6 | 44/0.4 | 0.8 | 15.0 | 416 | 50 | 30 | 0.69 |
4 x 10 | 74/0.4 | 1.0 | 18.2 | 632 | 50 | 41 | 1.15 |
4 x 16 | 120/0.4 | 1.0 | 20.8 | 893 | 40 | 58 | 1.84 |
4 x 25 | 185/0.4 | 1.2 | 24.7 | 1299 | 40 | 78 | 2.88 |
4 x 35 | 259/0.4 | 1.2 | 27.6 | 1714 | 40 | 99 | 4.03 |
4 x 50 | 370/0.4 | 1.4 | 32.5 | 2397 | 40 | 124 | 5.75 |
4 x 70 | 518/0.4 | 1.4 | 36.6 | 3195 | 30 | 156 | 8.05 |
4 x 95 | 703/0.4 | 1.6 | 42.1 | 4280 | 30 | 186 | 10.93 |
4 x 120 | 923/0.4 | 1.6 | 46.6 | 5432 | 30 | 218 | 13.80 |
4 x 150 | 1162/0.4 | 1.8 | 52.1 | 6810 | 30 | 251 | 17.25 |
4 x 185 | 1416/0.4 | 2.0 | 57.6 | 8286 | 20 | 285 | 21.28 |
4 x 240 | 1839/0.4 | 2.2 | 64.7 | 10613 | 20 | 338 | 27.60 |
4 x 300 | 1342/0.5 | 2.4 | 69.2 | 12124 | 20 | 387 | 34.50 |