NYYHY 1.5-300 mm² 0.6/1kV

CU/PVC/PVC-f
( Flexible Copper Conductor, PVC Insulated, PVC Sheath )
Standard Specification : SNI IEC 60502-1

Aplication :
Power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, distribution panels, luminaires and
other electrical used in dry indoor premises and Outdoor application.

Note :
Conductor Shape

Annealed plain copper wires bunch stranded
Flexible bunched wire

Standard Packing
1.5 - 16 sqmm supplied in coil@ 100 m
25 - 300 sqmm supplied in wooden drum
@ 1000 m

CONSTRUCTION AND ELECTRICAL DATA

Conductor Nominal Thickness Insulation Overall Diameter (approx.) Cable Weight (approx.) Min. Insulation DC.Resistance at 20ºC Max. Current Carrying Capacity at 30ºC Max. Short circuit current  at 1 sec.
Nominal Cross-sectional area No.of wire and diameter In Air
mm² mm mm mm kg/km A A kA
2 x 1.5 44/0.2 0.7 9.5 127 50 15 0.17
2 x 2.5 74/0.2 0.8 10.9 167 50 20 0.29
2 x 4 30/0.4 0.8 11.9 211 50 25 0.46
2 x 6 44/0.4 0.8 13.1 259 50 32 0.69
2 x 10 74/0.4 1.0 15.7 379 50 43 1.15
2 x 16 120/0.4 1.0 17.9 521 40 58 1.84
2 x 25 185/0.4 1.2 21.1 737 40 88 2.88
2 x 35 259/0.4 1.2 23.3 945 40 119 4.03
2 x 50 370/0.4 1.4 27.3 1302 40 150 5.75
2 x 70 518/0.4 1.4 30.7 1719 30 187 8.05
2 x 95 703/0.4 1.6 35.3 2294 30 223 10.93
2 x 120 923/0.4 1.6 39.1 2899 30 260 13.80
2 x 150 1162/0.4 1.8 43.5 2601 30 298 17.25
2 x 185 1416/0.4 2.0 48.1 4379 20 336 21.28
2 x 240 1839/0.4 2.2 54.1 5601 20 298 27.60
2 x 300 1342/0.5 2.4 57.7 6371 20 454 34.50