NYYHY 1.5-300 mm² 0.6/1kV
CU/PVC/PVC-f
( Flexible Copper Conductor, PVC Insulated, PVC Sheath )
Standard Specification : SNI IEC 60502-1
Aplication :
Power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, distribution panels, luminaires and
other electrical used in dry indoor premises and Outdoor application.
Note :
Conductor Shape
Annealed plain copper wires bunch stranded
Flexible bunched wire
Standard Packing
1.5 - 16 sqmm supplied in coil@ 100 m
25 - 300 sqmm supplied in wooden drum
@ 1000 m
CONSTRUCTION AND ELECTRICAL DATA
Conductor | Nominal Thickness Insulation | Overall Diameter (approx.) | Cable Weight (approx.) | Min. Insulation DC.Resistance at 20ºC | Max. Current Carrying Capacity at 30ºC | Max. Short circuit current at 1 sec. | |
Nominal Cross-sectional area | No.of wire and diameter | In Air | |||||
mm² | mm | mm | mm | kg/km | A | A | kA |
2 x 1.5 | 44/0.2 | 0.7 | 9.5 | 127 | 50 | 15 | 0.17 |
2 x 2.5 | 74/0.2 | 0.8 | 10.9 | 167 | 50 | 20 | 0.29 |
2 x 4 | 30/0.4 | 0.8 | 11.9 | 211 | 50 | 25 | 0.46 |
2 x 6 | 44/0.4 | 0.8 | 13.1 | 259 | 50 | 32 | 0.69 |
2 x 10 | 74/0.4 | 1.0 | 15.7 | 379 | 50 | 43 | 1.15 |
2 x 16 | 120/0.4 | 1.0 | 17.9 | 521 | 40 | 58 | 1.84 |
2 x 25 | 185/0.4 | 1.2 | 21.1 | 737 | 40 | 88 | 2.88 |
2 x 35 | 259/0.4 | 1.2 | 23.3 | 945 | 40 | 119 | 4.03 |
2 x 50 | 370/0.4 | 1.4 | 27.3 | 1302 | 40 | 150 | 5.75 |
2 x 70 | 518/0.4 | 1.4 | 30.7 | 1719 | 30 | 187 | 8.05 |
2 x 95 | 703/0.4 | 1.6 | 35.3 | 2294 | 30 | 223 | 10.93 |
2 x 120 | 923/0.4 | 1.6 | 39.1 | 2899 | 30 | 260 | 13.80 |
2 x 150 | 1162/0.4 | 1.8 | 43.5 | 2601 | 30 | 298 | 17.25 |
2 x 185 | 1416/0.4 | 2.0 | 48.1 | 4379 | 20 | 336 | 21.28 |
2 x 240 | 1839/0.4 | 2.2 | 54.1 | 5601 | 20 | 298 | 27.60 |
2 x 300 | 1342/0.5 | 2.4 | 57.7 | 6371 | 20 | 454 | 34.50 |